Technical Data

Dimensions:

  • Width Frame: 177 mm
  • Case: 164 mm
  • Height Frame: 177 mm (4U)
  • Case: 160 mm
  • Depth: 201 mm (153 + 48 mm)
  • Weight:
    • Complete protection relay: 4.1 kg
    • Plug-in unit only: 2.1 kg

Power Supply:

  • Type 1:
    • Nominal auxiliary voltage Un: 100, 110, 120, 220, 240 V AC, 50 and 60 Hz
    • Maximum interruption time in the auxiliary DC voltage without resetting the relay: 50 ms at Un
    • Auxiliary voltage variation: 38…110% of Un (38…264 V AC)
    • Start-up threshold: 19.2 V DC (24 V DC × 80%)
    • Burden of auxiliary voltage supply under quiescent (Pq)/operating condition:
      • DC <12.0 W (nominal)/<18.0 W (max)
      • AC <16.0 W (nominal)/<21.0 W (max)
    • Ripple in the DC auxiliary voltage: Max 15% of the DC value (at frequency of 100 Hz)
    • Fuse type: T4A/250 V
  • Type 2:
    • Nominal auxiliary voltage Un: 24, 30, 48, 60 V DC; 48, 60, 110, 125, 220, 250 V DC
    • Auxiliary voltage variation: 50…120% of Un (12…72 V DC); 80…120% of Un (38.4…300 V DC)

Energizing Inputs:

  • Rated frequency: 50/60 Hz
  • Current inputs:
    • Rated current, In: 0.2/1 A1), 1/5 A2)
    • Thermal withstand capability:
      • Continuously: 4 A (Type 1), 20 A (Type 2)
      • For 1 s: 100 A (Type 1), 500 A (Type 2)
    • Dynamic current withstand:
      • Half-wave value: 250 A (Type 1), 1250 A (Type 2)
    • Input impedance: <100 mΩ (Type 1), <20 mΩ (Type 2)
  • Voltage inputs:
    • Rated voltage: 60…210 V AC
    • Voltage withstand:
      • Continuous: 240 V AC
      • For 10 s: 360 V AC
    • Burden at rated voltage: <0.05 VA